Over 15 years experience of providing support of MEAN WELL Power Supplies
Overview
WDR-240-48 is the 48V output model of this series: rated current 5A, rated power 240W, typical efficiency 91%.
Features
- Single and two phase wide input range 180~550VAC
- Built-in active PFC circuit compliance to EN61000-3-2
- High efficiency 91% and low power dissipation
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508(industrial control equipment)approved
- EN61000-6-2(EN50082-2) industrial immunity level
- Built-in DC OK relay contact
- 100% full load burn-in test
- 3 years warranty
Specifications
OUTPUT
- DC VOLTAGE
- 48V
- RATED CURRENT
- 5A
- CURRENT RANGE
- 0 ~ 5A
- RATED POWER
- 240W
- RIPPLE & NOISE (max.)Note.2
- 150mVp-p
- VOLTAGE ADJ. RANGE
- 48 ~ 55V
- VOLTAGE TOLERANCENote.3
- ±1.0%
- LINE REGULATION
- ±0.5%
- LOAD REGULATION
- ±1.0%
- SETUP, RISE TIME
- 800ms, 150ms/400VAC 1500ms, 150ms/230VAC at full load
- HOLD UP TIME (Typ.)
- 18ms / 400VAC 18ms / 230VAC at full load
INPUT
- VOLTAGE RANGENote.6
- 180 ~ 550VAC 254 ~ 780VDC
- FREQUENCY RANGE
- 47 ~ 63Hz
- POWER FACTOR (Typ.)
- PF≥0.84/400VAC PF≥0.84/230VAC
- EFFICIENCY (Typ.)
- 91%
- AC CURRENT (Typ.)
- 1A/400VAC 2A/230VAC
- INRUSH CURRENT (Typ.)
- COLD START 50A
- LEAKAGE CURRENT
- <3.5mA / 530VAC
PROTECTION
- OVERLOAD
- 105 ~ 130% rated output power Protection type : Constant current limiting, unit will shut down after 3 sec. , auto-recovery after 1 minute if the fault condition is removed
- OVER VOLTAGE
- 56 ~ 65V Protection type : Shut down o/p voltage, auto-recovery after 1 minute if the fault condition is removed
- OVER TEMPERATURE
- 90℃±5℃ (TSW) detect on heatsink of power switch Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION
- DC OK REALY CONTACT RATINGS (max.)
- 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
ENVIRONMENT
- WORKING TEMP.Note.5
- -30 ~ +70℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 95% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -40 ~ +85℃, 10 ~ 95% RH
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃)
- VIBRATION
- Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC
- SAFETY STANDARDS
- Ul508 approved, IEC60950-1 CB approved by SIQ, design refer to GL;(meet EN60204-1)
- WITHSTAND VOLTAGE
- I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
- ISOLATION RESISTANCE
- I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSION
- Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
- EMC IMMUNITY
- Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A approved
OTHERS
- MTBF
- 141.1K hrs min. MIL-HDBK-217F (25 )
- DIMENSION
- 63*125.2*113.5mm (W*H*D)
- PACKING
- 1.06Kg; 12pcs/13.7Kg/1.06CUFT
Test conditions and notes6
- 1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25℃ of ambient temperature.
- 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- 3. Tolerance : includes set up tolerance, line regulation and load regulation.
- 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
- 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
- 6. Derating may be needed under low input voltage. Please check the derating curve for more details.
Technical drawings
Downloads
Datasheet1
Certificates3
Test reports1
FAQ
Can I use the WDR-240-48 for a 48V control panel or industrial automation cabinet?
Yes, this model is intended for DIN rail control cabinet use where a 48V DC output is required. It provides 240W at 48V with 5A output current, and its slim metal case is sized for rail-mounted panel layouts.
Is the WDR-240-48 suitable for building management or access control equipment that runs on 48V DC?
It can fit building management or access control systems that require a 48V DC supply and stay within 240W and 5A. The DIN rail format and 125.2 × 113.5 × 63.0 mm housing make it appropriate for organized enclosure installations.
Can this 48V DIN rail power supply be used for industrial communication or network devices inside a panel?
It is suitable for panel-mounted industrial equipment that needs 48V DC, provided the connected load does not exceed 240W or 5A. The wide 180-550VAC input also helps when the supply is used in industrial control environments with different AC input conditions.
Is the WDR-240-48 meant for open-air use, or should it be installed inside an enclosure?
This unit is better suited to protected control cabinets or enclosures rather than exposed open-air locations. Its operating temperature range is -30°C to +70°C, and the DIN rail metal-case design is aimed at enclosed industrial panel use.
How does the WDR-240-48 compare with other Mean Well WDR series models?
Within the WDR series, 48V options are WDR-60-48 at 60W, 1.25A; WDR-120-48 at 120W, 2.5A; WDR-240-48 at 240W, 5A; and WDR-480-48 at 480W, 10A. Other siblings are WDR-60-5 at 50W, 5V, 10A; WDR-60-12 at 60W, 12V, 5A; WDR-60-24 at 60W, 24V, 2.5A; WDR-120-12 at 120W, 12V, 10A; WDR-120-24 at 120W, 24V, 5A; WDR-240-24 at 240W, 24V, 10A; and WDR-480-24 at 480W, 24V, 20A.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other WDR-240 Models
1 other model| Model | Power | Voltage | Current | IP Rating | |
|---|---|---|---|---|---|
| Mean Well WDR-240-24 Single Output Industrial Power Supply 240W 24V 10A - DIN Rail | 240W | 24V | 10A | IP20 | View |
Please log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.