Over 15 years experience of providing support of MEAN WELL Power Supplies
Overview
DRP-240-48 is the 48V output model of this series: rated current 5A, rated power 240W, typical efficiency 85%.
Features
- Universal AC input / Full range
- Built in active PFC function
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508(industrial control equipment)approved
- LED indicator for power on
- 100% full load burn-in test
- Fixed switching frequency at 100KHz
- 3 years warranty
Specifications
OUTPUT
- DC VOLTAGE
- 48V
- RATED CURRENT
- 5A
- CURRENT RANGE
- 0 ~ 5A
- RATED POWER
- 240W
- RIPPLE & NOISE (max.)Note.2
- 150mVp-p
- VOLTAGE ADJ. RANGE
- 48 ~ 53V
- VOLTAGE TOLERANCENote.3
- ±1.0%
- LINE REGULATION
- ±0.5%
- LOAD REGULATION
- ±1.0%
- SETUP, RISE TIME
- 800ms, 40ms/230VAC 800ms, 40ms/115VAC at full load
- HOLD UP TIME (Typ.)
- 24ms/230VAC 24ms/115VAC at full load
INPUT
- VOLTAGE RANGENote.5
- 85 ~ 264VAC 120 ~ 370VDC
- FREQUENCY RANGE
- 47 ~ 63Hz
- POWER FACTOR (Typ.)
- 0.96/230VAC 0.99/115VAC at full load
- EFFICIENCY (Typ.)
- 85%
- AC CURRENT (Typ.)
- 2.8A/115VAC 1.4A/230VAC
- INRUSH CURRENT (Typ.)
- COLD START 27A/115VAC 45A/230VAC
- LEAKAGE CURRENT
- <3.5mA / 240VAC
PROTECTION
- OVERLOAD
- 105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed
- OVER VOLTAGE
- 54 ~ 60V Protection type : Shut down o/p voltage, re-power on to recover
- OVER TEMPERATURE
- Shut down o/p voltage, recovers automatically after temperature goes down
ENVIRONMENT
- WORKING TEMP.
- -10 ~ +70℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 90% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -20 ~ +85℃, 10 ~ 95% RH
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃)
- VIBRATION
- 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC (Note 4)
- SAFETY STANDARDS
- UL508, UL60950-1, EAC TP TC 004 approved
- WITHSTAND VOLTAGE
- I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
- ISOLATION RESISTANCE
- I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
- EMC EMISSION
- Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
- EMC IMMUNITY
- Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020
OTHERS
- MTBF
- 289.9Khrs min. MIL-HDBK-217F (25℃)
- DIMENSION
- 125.5*125.2*100mm (W*H*D)
- PACKING
- 1.2Kg; 12pcs/15.5Kg/1.49CUFT
Test conditions and notes6
- 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- 3. Tolerance : includes set up tolerance, line regulation and load regulation.
- 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
- 5. Derating may be needed under low input voltages. Please check the derating curve for more details.
- 6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
Technical drawings
Downloads
Datasheet1
Certificates5
Test reports1
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other DRP-240 Models
1 other model| Model | Power | Voltage | Current | IP Rating | |
|---|---|---|---|---|---|
| Mean Well DRP-240-24 AC-DC Industrial DIN rail power supply 240W 10A | 240W | 24V | 10A | IP20 | View |
Please log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.