Over 15 years experience of providing support of MEAN WELL Power Supplies
Overview
SHP-30K-55 is the model of this series: typical efficiency 95%.
SHP-30K-HV series is a 30KW high efficiency AC/DC power supply. This series operates for the wide range three phase AC input neutral is not needed, and offers the models with DC outputs (55V/115V/230V/380V) that mostly demanded by various industries. Can be working at ambient temperature up to 70℃ with forced air cooling. Moreover, SHP-30K-HV series provides vast design flexibility by equipping various built-in functions such as output programming, active current sharing, remote ON-OFF control, auxiliary power, and communication protocols, that will not only satisfy maker demand, but also enhance automation purpose. SHP-30K-HV can provide 120% short-duration peak power for motor applications and electromechanical loads requiring much higher power during start-up.
Features
- 3ψ 3-wire / △ or Y 340~530VAC or 3ψ 4-wire / Y 340~530VAC
- High efficiency up to 97%
- Up to 120% peak power capability
- 2U high 19-inch rack with forced air cooling
- Built-in CANBus/Optional PMBus/MODBUS-RTU/RS-485 protocol
- Output voltage and constant current level programmable
- Active current sharing up to 12 units(285KW) and more
- Built-in remote ON-OFF control / Auxiliary power / Alarm signal / Fan fail
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Double insulation for 55V model
- 5 years warranty
Specifications
OUTPUT
- DC VOLTAGE (factory default)
- 55V
- CURRENT (factory default)
- 346A
- CURRENT RANGE
- 0 ~ 346A
- RATED POWER (max.)
- 19000W
- FULL POWER VOLTAGE RANGE
- 48 ~ 57.6V
- RIPPLE & NOISE (max.)Note.2
- 0.55Vp-p
- VOLTAGE ADJ. RANGE
- 39 ~ 57.6V
- VOLTAGE ADJ. RANGE
- Can be adjusted via built-in potentiometer
- VOLTAGE TOLERANCENote.3
- ±1.0%
- LINE REGULATION
- ±0.5%
- LOAD REGULATION
- ±0.5%
- SETUP, RISE TIME
- 3000ms, 100ms at full load
- HOLD UP TIME (Typ.)
- 20ms / 400VAC at 75% load 16ms / 400VAC at full load
INPUT
- VOLTAGE RANGENote.5
- 3ψ 3-wire or 3ψ 4-wire / 340 ~ 530VAC
- FREQUENCY RANGE
- 47 ~ 63Hz
- POWER FACTOR (Typ.)
- ≧0.98/400VAC/480VAC at full load
- EFFICIENCY (Typ.)Note.6
- 95%
- AC CURRENT (Typ.)
- 30A/400VAC 25.2A/480VAC
- INRUSH CURRENT (Typ.)
- 60A/400VAC 80A/480VAC
- LEAKAGE CURRENT
- <14mA peak / 530VAC, <9mA rms / 530VAC
PROTECTION
- OVER LOAD
- Output power >105% rated for more than 5 seconds then shut down o/p voltage, re-power on to recover Protection type : Constant current limiting for output power >120% rated for more than 5 seconds and then shut down o/p voltage, re-power on to recover
- OVER VOLTAGE
- 60.5 ~ 69.1V Protection type : Shut down o/p voltage, re-power on to recover
- OVER TEMPERATURE
- Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION
- CURRENT SHARING
- Up to 12 units or more. Please refer to the Current share derating curve
- OUTPUT VOLTAGE PROGRAMMABLE
- Adjustment of output voltage is allowable between 50 ~ 120% of nominal output voltage. Please refer to the PV curve function manual
- CONSTANT CURRENT LEVEL PROGRAMMABLE
- Adjustment of constant current level is allowable between 1 ~ 100% of rated current. Please refer to the PC curve function manual
- AUXILIARY POWER(AUX)
- 12V@1.5A tolerance±5%, ripple 150mVp-p
- REMOTE ON-OFF CONTROL
- Please refer to the function manual.
- ALARM SIGNAL OUTPUT
- AC-OK, DC-OK, Fan Fail, T-ALARM. Please refer to the function manual.
- DC-OK/T-ALARM/FAN FAIL SIGNAL
- The TTL signal output, PSU turn on = -0.5 ~ 0.5V ; PSU turn off = 3.5 ~ 5.5V. Please refer to the function manual
- AC-OK SIGNAL
- The TTL signal output, PSU turn on = 3.5 ~ 5.5V ; PSU turn off = -0.5 ~ 0.5V. Please refer to the function manual
ENVIRONMENT
- WORKING TEMP.
- -30 ~ +70℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 90% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -40 ~ +85℃, 10 ~ 95% RH non-condensing
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃)
- VIBRATION
- 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC (Note 7)
- SAFETY STANDARDS
- UL62368-1, CAN/CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, EAC TP TC 004 approved
- WITHSTAND VOLTAGENote.4
- I/P-O/P:4.25KVAC I/P-FG:3KVAC O/P-FG:1.25KVAC
- ISOLATION RESISTANCENote.4
- I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSION
-
Parameter Standard Test Level Conducted BS EN/EN55032 (CISPR32) / EN55011 (CISPR11) Class A Radiated BS EN/EN55032 (CISPR32) / EN55011 (CISPR11) Class A Harmonic Current BS EN/EN61000-3-12 Voltage Flicker BS EN/EN61000-3-11 - EMC IMMUNITY
-
EN55024 , EN61204-3, EN61000-6-2
Parameter Standard Test Level ESD BS EN/EN61000-4-2 Level 3, 8KV air; Level 2, 4KV contact Radiated BS EN/EN61000-4-3 Level 3 EFT / Burst BS EN/EN61000-4-4 Level 3 Surge BS EN/EN61000-4-5 Level 4, 4KV/Line-Earth; Level 3, 2KV/Line-Line Conducted BS EN/EN61000-4-6 Level 3 Magnetic Field BS EN/EN61000-4-8 Level 4 Voltage Dips and Interruptions BS EN/EN61000-4-34 >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods
OTHERS
- MTBF
- 188.1K hrs min. Telcordia SR-332 (Bellcore) ; 20.9K hrs min. MIL-HDBK-217F (25℃)
- DIMENSION
- 540*424*83.5mm (L*W*H)
- PACKING
- 23.4Kg; 1pcs/23.4Kg/2.82CUFT
Test conditions and notes10
- 1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25℃ of ambient temperature.
- 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- 3. Tolerance :includes set up tolerance, line regulation and load regulation.
- 4. During withstand voltage and isolation resistance testing, the screw "A" shall be temporarily removed, and shall be installed back after the testing.
- 5. Derating may be needed under low input voltages. Please check the derating curve for more details.
- 6. The efficiency is measured at 75% load and 480VAC input.
- 7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 600mm*900mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to "EMI testing of component power supplies." (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf)
- 8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
- 9. If use PV signal to adjust Vo, under certain operations conditions, ripple noise of Vo might slightly go over rating defined in this specification.
- 10. Under light load condition, output voltage ripple will exceed specification. The behavior can be minimized by increasing the load.
Technical drawings
Typical applications
- Energy & power system for automation
- U.V or laser diode application
- Electrolysis system
- Laser processing machine
- Burn-in facility
- RF application
- EV charging station
Downloads
::specification::
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other SHP-30K Models
3 other models| Model | Power | Voltage | Current | |
|---|---|---|---|---|
| Mean Well SHP-30K-380 30KW High Efficiency Power Supply 55V Out 79A | 30000W | 380V | 79A | View |
| Mean Well SHP-30K-230 30KW High Efficiency Power Supply 230V Out 130.5A | 30000W | 230V | 130.5A | View |
| Mean Well SHP-30K-115 30KW High Efficiency Power Supply 115V Out 261A | 30000W | 115V | 261A | View |
Please log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.