Over 15 years experience of providing support of MEAN WELL Power Supplies
Overview
NDR-75-12 is the 12V output model of this series: rated current 6.3A, rated power 75.6W, typical efficiency 85.5%.
NDR-75 is one economical slim 75W Din rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 32mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. NDR-75 is designed with metal housing that enhances the unit's power dissipation. With working efficiency up to 89%, the entire series can operate at the ambient temperature between -20℃ and 70℃ under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make NDR-75 a very competitive power supply solution for industrial applications.
Features
- Universal AC input / Full range
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- 100% full load burn-in test
- 3 years warranty
Specifications
OUTPUT
- DC VOLTAGE
- 12V
- RATED CURRENT
- 6.3A
- CURRENT RANGE
- 0 ~ 6.3A
- RATED POWER
- 75.6W
- RIPPLE & NOISE (max.)Note.2
- 80mVp-p
- VOLTAGE ADJ. RANGE
- 12 ~ 14V
- VOLTAGE TOLERANCENote.3
- ±2.0%
- LINE REGULATION
- ±0.5%
- LOAD REGULATION
- ±1.0%
- SETUP, RISE TIME
- 1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load
- HOLD UP TIME (Typ.)
- 60ms/230VAC 12ms/115VAC at full load
INPUT
- VOLTAGE RANGENote.6
- 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
- FREQUENCY RANGE
- 47 ~ 63Hz
- EFFICIENCY (Typ.)
- 85.5%
- AC CURRENT (Typ.)
- 1.45A/115VAC 0.9A/230VAC
- INRUSH CURRENT (Typ.)
- 20A/115VAC 35A/230VAC
- LEAKAGE CURRENT
- <1mA / 240VAC
PROTECTION
- OVERLOAD
- 105 ~ 130% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed
- OVER VOLTAGE
- 14 ~ 17V Protection type : Shut down o/p voltage, re-power on to recover
- OVER TEMPERATURE
- Protection type : Shut down o/p voltage, re-power on to recover
ENVIRONMENT
- WORKING TEMP.
- -20 ~ +70℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 95% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -40 ~ +85℃, 10 ~ 95% RH
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃)
- VIBRATION
- Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC (Note 4)
- SAFETY STANDARDS
- UL508, TUV BS EN/EN62368-1, EAC TP TC 004 approved;(meet BS EN/EN60204-1)
- WITHSTAND VOLTAGE
- I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
- ISOLATION RESISTANCE
- I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSION
- Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
- EMC IMMUNITY
- Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), BS EN/EN61204-3, heavy industry level, EAC TP TC 020
OTHERS
- MTBF
- 2757.3K hrs min. Telcordia SR-332 (Bellcore) ; 486.2K hrs min. MIL-HDBK-217F (25℃)
- DIMENSION
- 32*125.2*102mm (W*H*D)
- PACKING
- 0.51Kg; 28pcs/15.3Kg/1.23CUFT
Test conditions and notes7
- 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
- 3. Tolerance : includes set up tolerance, line regulation and load regulation.
- 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
- 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
- 6. Derating may be needed under low input voltage. Please check the derating curve for more details.
- 7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
Technical drawings
Typical applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
Downloads
Certificates4
Test reports1
FAQ
Can I use the NDR-75-12 for a 12V PLC or control panel load?
Yes, this model is suited to 12V control panel and PLC-related loads that require 12VDC and stay within 6.3A and 75.6W. It is a DIN rail power supply with a slim 32.0 mm width, which helps in space-limited control cabinets. The input range is 90-264VAC.
Is the NDR-75-12 a good fit for 12V industrial automation devices inside a cabinet?
It can be used for 12V industrial automation equipment when the total DC demand does not exceed 6.3A or 75.6W. The DIN rail format, metal case, and slim size support use in compact industrial control enclosures. Its operating temperature range is -20°C to +70°C.
Can this 12V DIN rail power supply be used for building management or access control panels?
It can fit 12V building management or access control panels if the connected 12V load stays within 6.3A and 75.6W. The NDR-75-12 is built as a DIN rail power supply and measures 125.2 × 102.0 × 32.0 mm, which is useful where panel space is limited. The published certifications include UL508, TUV BS EN/EN62368-1, and EAC TP TC 004.
What is the difference between the NDR-75-12 and other NDR DIN rail models?
The NDR-75-12 is the 12V, 6.3A, 75.6W option in this group. Related models are NDR-75-24 at 24V, 3.2A, 76.8W; NDR-75-48 at 48V, 1.6A, 76.8W; NDR-120-12 at 12V, 10A, 120W; NDR-120-24 at 24V, 5A, 120W; NDR-120-48 at 48V, 2.5A, 120W; NDR-240-24 at 24V, 10A, 240W; NDR-240-48 at 48V, 5A, 240W; NDR-480-24 at 24V, 20A, 480W; and NDR-480-48 at 48V, 10A, 480W.
Is the NDR-75-12 suitable for use inside a control cabinet or enclosure?
This model is designed as a DIN rail power supply with a metal case and a slim 32.0 mm profile, so it fits well in control cabinets and enclosures. Its operating temperature range is -20°C to +70°C. The specs provided here do not list an external IP rating, so enclosure protection depends on the cabinet design rather than this product listing.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other NDR-75 Models
2 other models| Model | Power | Voltage | Current | IP Rating | |
|---|---|---|---|---|---|
| Mean Well NDR-75-24 Single Output Industrial Power Supply 75W 24V 3.2A - DIN Rail | 76.8W | 24V | 3.2A | IP20 | View |
| Mean Well NDR-75-48 Single Output Industrial Power Supply 75W 48V 1.6A - DIN Rail | 76.8W | 48V | 1.6A | IP20 | View |
Please log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.