Mean Well WDR-60-12 Single Output Industrial Power Supply 60W 12V 5A - DIN Rail

metal caseslim size1&2 phase180~550VAC wide inputhigh efficiency up to 93%
SKU WDR-60-12
Log in to see price Trade pricing & online ordering for account holders
Model

Select model — 2 in this family

WDR-60-12
In stock
|

Overview

WDR-60-12 is the 12V output model of this series: rated current 5A, rated power 60W, typical efficiency 86.5% / 400Vac.

WDR-60 series is a 60W DIN rail power supply with ultra-wide AC input range. It is suitable to be mounted on TS-35/7.5 or TS-35/15 rails. Main features are as following: it can accept 180~550Vac ultra-wide input voltage range for single phase or 2-phase system, easy to install DIN rail type, narrow width (32mm) in slim design, -30~+85°C wide range operating temp, 4.7KVAC high isolation voltage, operation at 2000m altitude, adjustable output voltage (+20% max.), high efficiency, low ripple & noise, complete protections and so on. WDR-60 is compliant with EN-61000-6-2 standard regarding immunity for industrial environments. It suitable for industrial automation, surveillance, telecommunication and more applications.

Features

  • 180 ~ 550Vac ultra wide input for 1-phase or 2-phase
  • 32mm slim width
  • 4.7KVac I/O high isolation(Reinforced isolation)
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • -30~+85°C ultra-wide operating temperature ( >+60°C derating)
  • Over voltage category Ⅲ
  • DC OK relay contact
  • DC output voltage adjustable(+20%)
  • 3 years warranty

Specifications

WDR-60-12Specifications from the official datasheet (2019-10-12 edition)Download datasheet PDF

OUTPUT

DC VOLTAGE
12V
RATED CURRENT
5A
CURRENT RANGE
0 ~ 5A
RATED POWER
60W
RIPPLE & NOISE (max.)Note.2
120mVp-p
VOLTAGE ADJ. RANGE
12 ~ 15V
VOLTAGE TOLERANCENote.3
±1.5%
LINE REGULATION
±0.5%
LOAD REGULATION
±0.5%
SETUP, RISE, HOLD UP TIME
1000ms, 70ms, 20ms/400Vac 2000ms, 70ms, 10ms/230Vac at full load

INPUT

VOLTAGE RANGENote.4
180 ~ 550Vac or 254 ~ 780Vdc
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
86.5% / 400Vac
AC CURRENT
0.4A/400Vac 0.7A/230Vac
INRUSH CURRENT (max.)
COLD START 50A /400Vac 30A/230Vac
LEAKAGE CURRENT
<2mA / 530Vac

PROTECTION

OVERLOAD
105 ~ 135% rated output power Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed
OVER VOLTAGE
16 ~ 18V Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
Protection type : Shut down o/p voltage, re-power on to recover

FUNCTION

DC OK SIGNAL
Relay contact rating(max.) : 30V / 1A resistive

ENVIRONMENT

WORKING TEMP.
-30 ~ +85℃ (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
STORAGE TEMP.
-40 ~ +85℃
TEMP. COEFFICIENT
±0.03%/℃ (0 ~ 60℃ )
VIBRATION
Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
OPERATING ALTITUDENote.5
2000 meters
OVER VOLTAGE CATEGORY
Ⅲ ; According to EN61558, EN50178, EN60664-1, EN62477-1, EN60204-1; altitude up to 2000 meters

SAFETY & EMC

SAFETY STANDARDS
UL61010, EN61558-2-16, EAC TP TC 004 approved; design refer to GL and EN60204-1(By request)
WITHSTAND VOLTAGE
I/P-O/P:4.7KVAC I/P-FG:2.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION
ParameterStandardTest Level
ConductedEN55032(CISPR32)Class B
RadiatedEN55032(CISPR32)Class B
Harmonic CurrentEN61000-3-2Class A
Voltage FlickerEN61000-3-3-------
EMC IMMUNITYNote 7

EN55024, EN55035, EN61000-6-2, EN61204-3

ParameterStandardTest Level
ESDEN61000-4-2Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated SusceptibilityEN61000-4-3Level 3, 10V/m, criteria A
EFT BurstsEN61000-4-4Level 3, 2KV/5KHz, criteria A
SurgeEN61000-4-5Level 4, 2KV/Line-Line, 4KV/Line-Earth, criteria A
ConductedEN61000-4-6Level 3, 10V, criteria A
Magnetic FieldEN61000-4-8Level 4, 30A/m, criteria A
Voltage Dips and interruptionsEN61000-4-11>95% dip 0. 5 periods, 30% dip 25 periods, >95% interruptions 250 periods

OTHERS

MTBF
313.68K hrs min. MIL-HDBK-217F (25℃)
DIMENSION
32*125.2*102mm (W*H*D)
PACKING
0.45Kg; 28pcs/13.6Kg/1.24CUFT
Test conditions and notes7
  1. 1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25℃ of ambient temperature.
  2. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.
  3. 3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. 4. Derating may be needed under low input voltage. Please check the derating curve for more details.
  5. 5. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
  6. 6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
  7. 7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)

Technical drawings

WDR-60-12 Block Diagram
Block Diagram
WDR-60-12 Derating Curve
Derating Curve
WDR-60-12 Mechanical Specification
Mechanical Specification

Typical applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

Downloads

FAQ

Can I use the WDR-60-12 for a compact 12V control panel application?

Yes, this model is suited to compact DIN rail control cabinet applications that require 12V DC. It delivers 60W at 12V with 5A output current, and its 125.2 × 102.0 × 32.0 mm slim profile helps in narrow panel layouts.

Is the WDR-60-12 suitable for alarm, monitoring, or auxiliary control devices in an industrial enclosure?

It can be used for 12V DC auxiliary loads in industrial or building control enclosures as long as total demand stays within 60W and 5A. The DIN rail format is useful when those devices are mounted alongside other panel components.

Can this 12V DIN rail supply be used in building management panels with low-power control hardware?

Yes, it is appropriate for low-power 12V DC building management and control hardware that fits within its rated output. Its metal case and slim size support use inside space-limited control cabinets.

Is the WDR-60-12 designed for control cabinet use in harsh temperature ranges?

Yes, it is intended for enclosed cabinet use and has an operating temperature range of -30°C to +85°C. That is the widest temperature range among the listed WDR models here, which helps in demanding indoor industrial environments.

How does the WDR-60-12 compare with the other WDR series models?

For 12V outputs, the listed WDR options are WDR-60-12 at 60W, 5A and WDR-120-12 at 120W, 10A. The rest of the sibling lineup is WDR-60-5 at 50W, 5V, 10A; WDR-60-24 at 60W, 24V, 2.5A; WDR-60-48 at 60W, 48V, 1.25A; WDR-120-24 at 120W, 24V, 5A; WDR-120-48 at 120W, 48V, 2.5A; WDR-240-24 at 240W, 24V, 10A; WDR-240-48 at 240W, 48V, 5A; WDR-480-24 at 480W, 24V, 20A; and WDR-480-48 at 480W, 48V, 10A.

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Union Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

{ "id":8318606115115, "variants" :[{ "context":"default", "variant_id": 45222698680619, "sku":"WDR-60-12", "inventory_qty" : 17, "customer" :false, "custom_html" :"\u003ca class=\"text-current logged-out-price logged-out\" href=\"https:\/\/wellforces.co.nz\/customer_authentication\/redirect?locale=en\u0026region_country=NZ\"\u003e\n \u003cspan \u003ePlease \u003c\/span\u003e \u003cspan class=\"login-text\"\u003eLogin\u003c\/span\u003e \u003cspan\u003e for Pricing\u003c\/span\u003e\n \u003c\/a\u003e", "volume_html" :"\u003cvolume-pricing class=\"parent-display inside_product_form\" id=\"volume-pricing-main\" \u003e\u003c\/volume-pricing\u003e" } ] }
Mean Well WDR-60-12 Single Output Industrial Power Supply 60W 12V 5A - DIN Rail
Mean Well

Mean Well WDR-60-12 Single Output Industrial Power Supply 60W 12V 5A - DIN Rail

WDR-60-12 is the 12V output model of this series: rated current 5A, rated power 60W, typical efficiency 86.5% / 400Vac.

WDR-60 series is a 60W DIN rail power supply with ultra-wide AC input range. It is suitable to be mounted on TS-35/7.5 or TS-35/15 rails. Main features are as following: it can accept 180~550Vac ultra-wide input voltage range for single phase or 2-phase system, easy to install DIN rail type, narrow width (32mm) in slim design, -30~+85°C wide range operating temp, 4.7KVAC high isolation voltage, operation at 2000m altitude, adjustable output voltage (+20% max.), high efficiency, low ripple & noise, complete protections and so on. WDR-60 is compliant with EN-61000-6-2 standard regarding immunity for industrial environments. It suitable for industrial automation, surveillance, telecommunication and more applications.

Features

  • 180 ~ 550Vac ultra wide input for 1-phase or 2-phase
  • 32mm slim width
  • 4.7KVac I/O high isolation(Reinforced isolation)
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • -30~+85°C ultra-wide operating temperature ( >+60°C derating)
  • Over voltage category Ⅲ
  • DC OK relay contact
  • DC output voltage adjustable(+20%)
  • 3 years warranty

Typical applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

Model

  • 60W 12V
  • 120W 12V