Overview

The ICL-28 is a 28A inrush current limiter that can be used to reduce the high starting current due to capacitive load causing the circuit breaker to be false triggered. Several power supplies can be installed on the same AC line after the implementation of an ICL-28.

Features

  • 48A inrush limiting current, 28A continuous
  • 180~264VAC AC input
  • Integrated bypass relay, no simple NTC
  • Internal thermal protection
  • Installed on DIN Rail TS-35/7.5 or 15 (ICL-28R)
  • -30~+70°C wide working temperature
  • Over voltage category Ⅲ
  • Operating altitude up to 5000 meters(Note. 2)
  • 3 years warranty

Specifications

ICL-28LSpecifications from the official datasheet (2026-04-03 edition)

SPECIFICATION

AC INPUT VOLTAGE
180 ~ 264VAC
AC LINE FREQUENCY
47 ~ 63Hz
INRUSH CURRENT LIMITING
48A
AC CONTINUOUS RATED CURRENT
28A continuous
AC INPUT POWER
6440VA (28A x 230VAC)
AC INPUT CONSUMPTION
<2W at 264VAC, 50Hz input
INTERNAL RELAY LIMITING TIME (TON POWER ON)
150±50ms
INTERNAL RELAY LIMITING CYCLES
3 cycle / 1 min
INTERNAL RELAY RELEASE TIME
100±50ms
INTERNAL PROTECTION
Thermal fuse protects overload and fire
ALLOWED CAPACITIVE LOAD
6000μF max.
WORKING TEMP.
-30 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
STORAGE TEMP.
-40 ~ +85℃
TEMP. COEFFICIENT
±0.03%/℃ (0 ~ 60℃) RH non-condensing
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDENote. 2
5000 meters
OVER VOLTAGE CATEGORY
Ⅲ; According to IEC62368-1; altitude up to 5000 meters
POLLUTION DEGREE
2
SAFETY STANDARDS
LVD BS EN/EN62368-1 approved
SAFETY & EMC EMC EMISSIONNote.3
ParameterStandardTest Level
ConductedBS EN/EN55032Class B
RadiatedBS EN/EN55032Class B
Harmonic CurrentBS EN/EN61000-3-2Class A
Voltage FlickerBS EN/EN61000-3-3-------
SAFETY & EMC EMC IMMUNITYNote.3

BS EN/EN55035, BS EN/EN61000-6-2

ParameterStandardTest Level
ESDBS EN/EN61000-4-2Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated SusceptibilityBS EN/EN61000-4-3Level 3, criteria A
EFT/BurestBS EN/EN61000-4-4Level 3, criteria A
SurgeBS EN/EN61000-4-5Level 4,2KV/L-N, criteria A
ConductedBS EN/EN61000-4-6Level 3, criteria A
Magnetic FieldBS EN/EN61000-4-8Level 4, criteria A
Voltage Dips and interruptionsBS EN/EN61000-4-11>95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods
MTBF
6781.7K hrs min. Telcordia SR-332 (Bellcore) ; 1626.6K hrs min. MIL-HDBK-217F (25℃)
DIMENSION
175*42*24mm (L*W*H)
PACKING
0.155Kg; 84pcs/14Kg/0.91CUFT
Test conditions and notes3
  1. 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
  2. 2. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
  3. 3. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

Technical drawings

ICL-28L BLOCK DIAGRAM
BLOCK DIAGRAM
ICL-28L Derating Curve
Derating Curve
ICL-28L APPLICATION DIAGRAM
APPLICATION DIAGRAM
ICL-28L MECHANICAL SPECIFICATION
MECHANICAL SPECIFICATION

Typical applications

  • Allow connecting multiple power supply at same line
  • Allows smaller and faster Circuit Breaker
  • Capacitive load
  • Protects against unintended trigger of circuit breaker

Downloads

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Union Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

{ "id":8443329577259, "variants" :[{ "context":"default", "variant_id": 45714900975915, "sku":"ICL-28L", "inventory_qty" : 0, "customer" :false, "custom_html" :"\u003ca class=\"text-current logged-out-price logged-out\" href=\"https:\/\/wellforces.co.nz\/customer_authentication\/redirect?locale=en\u0026region_country=NZ\"\u003e\n \u003cspan \u003ePlease \u003c\/span\u003e \u003cspan class=\"login-text\"\u003eLogin\u003c\/span\u003e \u003cspan\u003e for Pricing\u003c\/span\u003e\n \u003c\/a\u003e", "volume_html" :"\u003cvolume-pricing class=\"parent-display inside_product_form\" id=\"volume-pricing-main\" \u003e\u003c\/volume-pricing\u003e" } ] }
Mean Well ICL-28L AC Inrush Current Limiter
Mean Well

Mean Well ICL-28L AC Inrush Current Limiter

The ICL-28 is a 28A inrush current limiter that can be used to reduce the high starting current due to capacitive load causing the circuit breaker to be false triggered. Several power supplies can be installed on the same AC line after the implementation of an ICL-28.

Features

  • 48A inrush limiting current, 28A continuous
  • 180~264VAC AC input
  • Integrated bypass relay, no simple NTC
  • Internal thermal protection
  • Installed on DIN Rail TS-35/7.5 or 15 (ICL-28R)
  • -30~+70°C wide working temperature
  • Over voltage category Ⅲ
  • Operating altitude up to 5000 meters(Note. 2)
  • 3 years warranty

Typical applications

  • Allow connecting multiple power supply at same line
  • Allows smaller and faster Circuit Breaker
  • Capacitive load
  • Protects against unintended trigger of circuit breaker
View product