Over 15 years experience of providing support of MEAN WELL Power Supplies
Overview
SDR-480-48 is the 48V output model of this series: rated current 10A, rated power 480W, typical efficiency 94%.
Features
- High efficiency 94% and low power dissipation
- 150% peak load capability
- Built-in active PFC function, PF>0.94
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508(industrial control equipment)approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- Built-in DC OK relay contact
- 100% full load burn-in test
- 3 years warranty
Specifications
OUTPUT
- DC VOLTAGE
- 48V
- RATED CURRENT
- 10A
- CURRENT RANGE
- 0 ~ 10A
- RATED POWER
- 480W
- PEAK CURRENT
- 15A
- PEAK POWERNote.6
- 720W (3sec.)
- RIPPLE & NOISE (max.)Note.2
- 120mVp-p
- VOLTAGE ADJ. RANGE
- 48 ~ 55V
- VOLTAGE TOLERANCENote.3
- ±1.0%
- LINE REGULATION
- ±0.5%
- LOAD REGULATION
- ±1.0%
- SETUP, RISE TIME
- 1500ms, 150ms/230VAC 3000ms, 150ms/115VAC at full load
- HOLD UP TIME (Typ.)
- 14ms/230VAC at full load
INPUT
- VOLTAGE RANGENote.7
- 90 ~ 264VAC 127 ~ 370VDC
- FREQUENCY RANGE
- 47 ~ 63Hz
- POWER FACTOR (Typ.)
- 0.94/230VAC 0.99/115VAC at full load
- EFFICIENCY (Typ.)
- 94%
- AC CURRENT (Typ.)
- 5A/115VAC 2.5A/230VAC
- INRUSH CURRENT (Typ.)
- 40A/115VAC 80A/230VAC
- LEAKAGE CURRENT
- <0.8mA / 240VAC
PROTECTION
- OVERLOAD
- Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery >150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
- OVER VOLTAGE
- 56 ~ 65V Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery
- OVER TEMPERATURE
- Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION
- DC OK REALY CONTACT RATINGS (max.)
- 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
ENVIRONMENT
- WORKING TEMP.Note.5
- -25 ~ +70℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 95% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -40 ~ +85℃, 10 ~ 95% RH
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃)
- VIBRATION
- Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC (Note 4)
- SAFETY STANDARDS
- UL508, TUV BS EN/EN62368-1, AS/NZS 62368.1, EAC TP TC 004 , BSMI CNS15598-1 approved ; (meet BS EN/EN60204-1)
- WITHSTAND VOLTAGE
- I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
- ISOLATION RESISTANCE
- I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSION
- Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS15936
- EMC IMMUNITY
- Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), BS EN/EN61204-3, heavy industry level, EAC TP TC 020, SEMI F47 approved
OTHERS
- MTBF
- 964.2K hrs min. Telcordia SR-332 (Bellcore) ; 91.9K hrs min. MIL-HDBK-217F (25℃)
- DIMENSION
- 85.5*125.2*128.5mm (W*H*D)
- PACKING
- 1.6Kg; 8pcs/13.8Kg/0.9CUFT
Test conditions and notes8
- 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
- 3. Tolerance : includes set up tolerance, line regulation and load regulation.
- 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
- 5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
- 6. 3 seconds peak power max. and the average output power should not exceed the rate power.
- 7. Derating may be needed under low input voltage. Please check the derating curve for more details.
- 8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
Technical drawings
Downloads
Certificates5
Test reports1
FAQ
Can the SDR-480-48 power a 48V PLC or industrial automation panel?
Yes. The SDR-480-48 is a 48V DIN rail power supply rated for 480W and 10A, which fits 48V control panels, PLC cabinets, and industrial automation assemblies that need that voltage and current capacity. Its DIN rail form factor also suits panel layouts where organized cabinet mounting is required.
Is the SDR-480-48 suitable for 48V building management and control cabinets?
It can be used in 48V building management and control cabinet applications that require up to 480W and 10A output. The unit accepts 90-264VAC input and is built as a DIN rail industrial power supply, so it matches centralized cabinet power designs using standard AC mains input.
Can I use the SDR-480-48 for 48V relays, controllers, and panel devices in one enclosure?
Yes, if the combined 48V load stays within 480W and 10A. This model is intended for DIN rail mounting, so it fits multi-device control enclosures where several 48V panel components are powered from one cabinet supply.
Which SDR series models are available if I need a different voltage or power level than the SDR-480-48?
The SDR-480 series datasheet lists one other model: the SDR-480-24 at 480W, 24V, 20A (adjustable 24 ~ 28V). It shares the same 90-264VAC input, 94% typical efficiency, 720W (3 sec.) peak power and 85.5 x 125.2 x 128.5 mm housing as the SDR-480-48.
Is the SDR-480-48 meant for open environments or for use inside a control cabinet?
This model is generally suited to control cabinet and enclosure use, with an operating temperature range of -25°C to +70°C (refer to the derating curve). Its industrial DIN rail format and 85.5 x 125.2 x 128.5 mm (W x H x D) size make it a cabinet-mounted power supply rather than a free-standing open-environment unit.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other SDR-480 Models
1 other model| Model | Power | Voltage | Current | IP Rating | |
|---|---|---|---|---|---|
| Mean Well SDR-480-24 Single Output Industrial Power Supply 480W 24V 20A - DIN Rail | 480W | 24V | 20A | IP20 | View |
Please log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.