Overview
NTN-5K-124CAN is the model of this series: typical efficiency 89%.
NTN-5K is a 5KW highly reliable off-grid true sine wave DC-AC power inverter with built-in AC charger and UPS function(AC by-pass). Its key features include: digital design with MCU control, streamlined control circuitry that quickly responds to environmental changes and improves reliability, high quality fan with low acoustic noise, 10KW peak power, adjustable AC output voltage and frequency, -30~+70℃ wide. Operating temperature range, complete protection features, and etc. Combined with batteries, the NTN-5K is suitable for use in residential, commercial, marine, automobile, mine, construction site, and remote areas with no access to utility power, and the output can be used to power fans, TV, radio, phone charger, PC/laptop, lighting, induction stove, air conditioner, electromechanical tool, communication equipment, power distribution cabinet, outdoor camping equipment, marine AC power, factory equipment, and etc.
Features
- Combining AC/DC charger, DC/AC Inverter, AC by-pass & support external MPPT solar charger
- AC utility charge up to 4520W
- UPS function (AC by-pass) without interruption, transfer time <10ms
- True sine wave output (THD<3%)
- High surge power up to 10KW
- Parallel synchronized operation up to 30KW (5+1 unit)
- Temperature controlled cooling fan
- AC output voltage and frequency selectable by DIP S.W
- Protections : Input : Reverse polarity / DC low alarm / DC low shutdown / Over voltage Output : Short circuit / Overload / Over temp.
- Battery over discharge protection (low voltage disconnect)
- -30℃~+70℃ wide operating temperature
- Suitable for lead-acid or li-ion batteries
- Support MODBus-RTU(RS-485) or CANBus protocol communication
- Graphical user interface controller for status monitoring and control CMU2E/CMU2E-R
- Conformal coating
- 5 years warranty
Specifications
AC OUTPUT
- RATED POWER(Continuous)
- 4000W
- OVER RATED POWER(3 Min.)
- 4600W
- PEAK POWER(10 Sec.)
- 5600W
- SURGE POWER(30 Cycles)
- 7000W
- AC VOLTAGE
- Default setting set at 110VAC 100 / 110 / 115 / 120Vac selectable by DIP S.W
- FREQUENCY
- Default setting set at 60±0.1Hz 50/60Hz selectable by DIP S.W
- WAVEFORMNote. 1
- True sine wave (THD<3%)
- AC REGULATION
- ±3.0% at rated input voltage
DC INPUT
- DC VOLTAGE
- 24Vdc
- VOLTAGE RANGE (Typ.)
- 19 ~ 33Vdc
- DC CURRENT (Typ.)
- 200A
- NO LOAD DISSIPATION (Typ.) NON-SAVING MODE
- 2.5A
- NO LOAD DISSIPATION (Typ.) SAVING MODENote. 5
- Default disable, auto detect AC output load≦10W will be changed to saving mode <25W
- POWER OFF CURRENT DRAW
- ≦2mA
- EFFICIENCY (Typ.)Note. 1
- 89%
- BATTERY TYPES
- Lead Acid or li-ion
PROTECTION
- DC INPUT LOW ALARM
- 22±0.5Vdc
- DC INPUT LOW SHUTDOWN
- 19±0.5Vdc
- DC INPUT LOW RESTART
- 25±0.5Vdc
- DC INPUT HIGH ALARM
- 31±0.5Vdc
- DC INPUT HIGH SHUTDOWN
- 33±0.5Vdc
- DC INPUT HIGH RESTART
- 30±0.5Vdc
- REVERSE POLARITY
- No damage, re-power on to recover after fault condition is removed
- OVER TEMPERATURE
- Shut down o/p voltage, recovers automatically after temperature goes down
- OUTPUT SHORT
- Shut down o/p voltage, re-power on to recover
- OVER LOAD (Typ.)
- 105 ~ 115% load for 180 sec., 115% ~ 150% load for 10 sec. Protection type : Shut down o/p voltage, re-power on to recover
- CIRCUIT BREAKER
- 50A
FUNCTION
- REMOTE CONTROL
- Set remote ON/OFF control by front panel dry contact connector(by RELAY), Open : AC output OFF ; Short : AC output ON
- COMMUNICATION
- MODBus-RTU (RS-485) / CANBus
AC UPS MODE
- AC INPUT RANGE
- 100/110/115/120Vac±16%, recover±13%
- FREQUENCY RANGE
- 45 ~ 65Hz
- TRASFER TIME(Typ.)
- 10ms inverter AC by pass
AC CHARGER
- BOOST CHARGE VOLTAGE
- Default 28.8Vdc
- FLOAT CHARGE VOLTAGE
- Default 27.6Vdc
- CHARGE VOLTAGE RANGE
- 20 ~ 30Vdc
- CONSTANT CURRENT
- 120A
- MAX. CHARGE POWER
- 3600W
- TEMPERATURE COMPENSATION
- By external NTC
- POWER FACTOR (Typ.)
- PF>0.98/115VAC at full load
- EFFICIENCY (Typ.)
- 89%
- AC CURRENT (Typ.)
- 20A/110VAC
- INRUSH CURRENT (Typ.)
- 25A/110VAC
- LEAKAGE CURRENT(Peak)
- 4.7mA/264VAC
ENVIRONMENT
- WORKING TEMP.
- -30 ~ +70℃(Refer to “Derating curve”)
- WORKING HUMIDITY
- 20% ~ 90% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -30 ~ +70℃ / -22 ~ +158℉, 10 ~ 95% RH non-condensing
- VIBRATION
- 10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC
- SAFETY STANDARDS
- CB IEC62368-1, UL62368-1, CSA C22.2 No. 62368-1 , TUV BS EN/ EN62368-1 , EAC TP TC 004 approved
- WITHSTAND VOLTAGENote. 6
- DC I/P - AC:3.0KVAC AC - FG:1.5KVAC
- ISOLATION RESISTANCENote. 6
- DC I/P - AC O/P, DC I/P - FG, AC O/P - FG: 100M ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSIONNote.4
-
Parameter Standard Test Level Radiated FCC Class A Conducted FCC Class A
OTHERS
- MTBF
- 200.9K hrs min. Telcordia TR/SR-332 (Bellcore) ; 17.8K hrs min. MIL-HDBK-217F (25℃)
- DIMENSION
- 460*211*83.5mm (L*W*H)
- PACKING
- 10.5Kg; 1pcs/ 10.5Kg/ 1.25CUFT
Test conditions and notes6
- 1.Efficiency, AC regulation and THD are tested by 75% load, linear load at 25Vdc/50Vdc/400Vdc input voltage.
- 2.All parameters not specified above are measured at 25Vdc/50Vdc/400Vdc input and 25℃ of ambient temperature and set to factory setting.
- 3.The tolerance of each voltage value by models is: 224→±0.5V; 248→±1V; 2380→±5V.
- 4.The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf)
- 5.Saving mode only activates when the unit is used independently and the RPL switch is in the ON position.
- 6.During withstand voltage and isolation resistance testing, the screw "A" shall be temporarily removed, and shall be installed back after the testing.
Technical drawings
Typical applications
- Home and office appliance
- Power tools
- Portable equipment
- Vehiclc
- Yacht
- Off-grid solar power system
- Wireless network
- Telecom or datacom system
Downloads
::specification::
FAQ
What kind of product is the Mean Well NTN-5K-124CAN?
The NTN-5K-124CAN is a multi-function power unit that combines an AC-DC charger, a DC-AC true sine wave inverter, and AC bypass for the load in one model. It is designed for 24V DC input systems and provides 110V AC output. This makes it suitable for backup power and power conversion applications where charger and inverter functions are both needed.
Is the NTN-5K-124CAN a pure sine wave inverter?
Yes. This model provides pure sine wave AC output with total harmonic distortion below 3%. That is useful for loads that need cleaner AC power than modified sine wave designs typically provide.
Can the NTN-5K-124CAN be used in UPS or backup power applications?
Yes, this model is built for that type of use because it combines an inverter, a high-power AC charger, and AC bypass for the load. Its built-in charger is rated up to 3600W (120A constant current), and the unit also supports remote ON/OFF control. Those features make it a practical choice for battery-backed power systems that need continuous AC output support.
What battery types are compatible with the NTN-5K-124CAN?
Mean Well specifies this model as compatible with both lead acid and li-ion batteries. The DC input range for the 24V version is 19 to 33Vdc. Buyers should match the battery system voltage to the 24V input version of this inverter/charger.
Can multiple NTN-5K-124CAN units be used together for higher capacity?
Yes. Mean Well states that up to 6 units of AC output can be paralleled, with total output current limited to the rated current per unit x number of units x 95%. The product information also notes that 3 NTN-5K units can be configured for 3-phase 4-wire output, and two 124 units for split-phase 1Ø 3-wire.
What protections are built into the NTN-5K-124CAN?
This model includes multiple built-in protections on both the DC input and AC output sides. DC-side protections include reverse polarity, low voltage alarm (22V) and shutdown (19V), and high voltage alarm (31V) and shutdown (33V), while AC-side protections include short circuit, overload, and over temperature, plus a 50A circuit breaker. These protection functions are part of the standard design for this model.
Is the NTN-5K-124CAN suitable for demanding temperature environments?
Yes. This model is rated for operation from -30C to +70C (with load derating per the derating curve), which is a wider temperature range than many standard indoor power units. Working humidity is 20% to 90% RH non-condensing, so it should be installed where condensation cannot form.
Does the NTN-5K-124CAN support remote monitoring or system communication?
Yes. The NTN-5K-124CAN supports Modbus-RTU over RS-485 and CAN bus communication. It also has built-in remote ON/OFF control, which can be useful in monitored or centrally managed power systems.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other NTN-5K Models
9 other modelsPlease log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.