MDR-60-48 is the 48V output model of this series: rated current 1.25A, rated power 60W, typical efficiency 87%.

Features

  • Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Class I, Div 2 Hazardous Locations T4
  • LED indicator for power on
  • DC OK relay contact
  • No load power consumption<0.75W
  • 100% full load burn-in test
  • 3 years warranty

Specifications

MDR-60-48Specifications from the official datasheet (2025-07-25 edition)

OUTPUT

DC VOLTAGE
48V
RATED CURRENT
1.25A
CURRENT RANGE
0 ~ 1.25A
RATED POWER
60W
RIPPLE & NOISE (max.)Note.2
200mVp-p
VOLTAGE ADJ. RANGE
48 ~ 56V
VOLTAGE TOLERANCENote.3
±1.0%
LINE REGULATION
±1.0%
LOAD REGULATION
±1.0%
SETUP, RISE TIMENote.5
500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)
50ms/230VAC 20ms/115VAC at full load

INPUT

VOLTAGE RANGE
85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
87%
AC CURRENT (Typ.)
1.8A/115VAC 1A/230VAC
INRUSH CURRENT (Typ.)
COLD START 30A/115VAC 60A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC

PROTECTION

OVERLOAD
105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE
57.6 ~ 64.8V Protection type : Shut down o/p voltage, re-power on to recover

FUNCTION

DC OK SIGNAL
Relay contact rating(max.): 30V/1A resistive

ENVIRONMENT

WORKING TEMP.
-20 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY
-40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT
±0.03%/℃ (0 ~ 50℃)
VIBRATION
Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6

SAFETY & EMC (Note 4)

SAFETY STANDARDS
UL508, UL62368-1, TUV BS EN/EN62368-1,Class I, Div. 2 Group A, B, C, D Hazardous Locations T4, EAC TP TC 004, BSMI CNS14336-1, AS/NZS 60950.1 , BIS IS13252(Part1): 2010/IEC 60950-1:2005(except 48V) approved
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION
Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B
EMC IMMUNITY
Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11, BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3, heavy industry level, EAC TP TC 020

OTHERS

MTBF
2355.2K hrs min. Telcordia SR-332 (Bellcore) ; 489.9K hrs min. MIL-HDBK-217F (25℃)
DIMENSION
40*90*100mm (W*H*D)
PACKING
287g; 42pcs/13.05Kg/0.82CUFT
Test conditions and notes6
  1. 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
  2. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
  3. 3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
  5. 5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
  6. 6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

Technical drawings

MDR-60-48 Mechanical Specification
Mechanical Specification
MDR-60-48 Block Diagram
Block Diagram
MDR-60-48 Derating Curve
Derating Curve

Downloads

FAQ

Can I use the MDR-60-48 for a 48V PLC cabinet or industrial control system?

Yes, it is intended for 48VDC applications and can supply up to 1.25A with a 60W rating. That makes it a fit for 48V industrial control, PLC cabinet, and automation equipment that stays within those limits. The DIN rail format also suits panel-based installations.

Is the MDR-60-48 suitable for building automation panels that use 48VDC devices?

It can be used in building automation and control cabinets where the system requires 48VDC and the load is no more than 1.25A or 60W. The 85-264VAC input supports a broad AC input range for panel power conversion. Its 40 mm wide housing helps when enclosure space is constrained.

Can this power supply be used for 48V industrial communication or control equipment on DIN rail?

Yes, it is appropriate for 48V industrial communication or control equipment when the total demand remains within 60W and 1.25A. The single-output DIN rail design is intended for orderly mounting inside automation cabinets. The compact 100.0 × 90.0 × 40.0 mm size is useful in dense control layouts.

Is the MDR-60-48 a good choice when I need a slim 48V power supply in a crowded enclosure?

Yes, this unit combines a 48V output with a compact DIN rail housing that measures 100.0 × 90.0 × 40.0 mm. That makes it practical for tight control cabinets where space planning matters. It still provides up to 1.25A and 60W in that compact form.

Should the MDR-60-48 be used inside a control cabinet or in exposed environments?

This model is best suited to installation inside a control cabinet or protective enclosure because no exposed-use IP rating is listed in the provided specs. Its operating temperature range is -20°C to +70°C, with output derating at higher temperatures per the derating curve, which supports enclosed industrial conditions. For direct outdoor exposure, buyers usually need a supply with a stated environmental protection rating.

What are the main differences between the MDR-60-48 and other MDR series options?

Within the MDR-60 series, the MDR-60-48 provides 60W at 48V and 1.25A. The other models on the same sheet are the MDR-60-5 at 50W, 5V, 10A; the MDR-60-12 at 60W, 12V, 5A; and the MDR-60-24 at 60W, 24V, 2.5A.

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Union Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

{ "id":8318588059947, "variants" :[{ "context":"default", "variant_id": 45222638846251, "sku":"MDR-60-48", "inventory_qty" : 0, "customer" :false, "custom_html" :"\u003ca class=\"text-current logged-out-price logged-out\" href=\"https:\/\/wellforces.co.nz\/customer_authentication\/redirect?locale=en\u0026region_country=NZ\"\u003e\n \u003cspan \u003ePlease \u003c\/span\u003e \u003cspan class=\"login-text\"\u003eLogin\u003c\/span\u003e \u003cspan\u003e for Pricing\u003c\/span\u003e\n \u003c\/a\u003e", "volume_html" :"\u003cvolume-pricing class=\"parent-display inside_product_form\" id=\"volume-pricing-main\" \u003e\u003c\/volume-pricing\u003e" } ] }
Mean Well MDR-60-48 Single Output Industrial Power Supply 60W 48V 1.25A - DIN Rail
Mean Well

Mean Well MDR-60-48 Single Output Industrial Power Supply 60W 48V 1.25A - DIN Rail

MDR-60-48 is the 48V output model of this series: rated current 1.25A, rated power 60W, typical efficiency 87%.

Features

  • Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Class I, Div 2 Hazardous Locations T4
  • LED indicator for power on
  • DC OK relay contact
  • No load power consumption<0.75W
  • 100% full load burn-in test
  • 3 years warranty

Model

  • 40W 48V
  • 100W 48V
  • 60W 48V