Over 15 years experience of providing support of MEAN WELL Power Supplies
Overview
NSP-2400-24 is the 24V output model of this series: rated power 2400W, typical efficiency 91%.
The NSP-2400 series is a 2400W AC/DC power supply with PFC function, designed for high reliability and suitable for multiple industries. Key features include: compact size (325.8*107*41mm) for better space utilization in system installations, ultra-wide input range of 85~305Vac for global compatibility, up to 93% efficiency , programmable output voltage (0~120%) and current (0~100%), constant current design with 200% peak power capability, parallel output capacity up to 9600W, built-in CANBus communication interface, wide operating temperature range from -40 to +85℃ (+60℃ at full load), compliance with OVCⅢ, built-in Remote Control /Remote Sense/DC OK signal/auxiliary power, internal PCB coating, complete protections, certifications for multiple safety standards including 62368-1, 60601-1, 61558-1, 60335-1, 62477-1, and 61010-1, as well as 2 X MOPP compliance and extremely low leakage current (<500μA). It is suitable for BF-rated medical equipment and comes with a 5-years warranty, making it a highly cost-effective solution for industrial power supply needs.
Features
- 85~305Vac input with PFC(277Vac available)
- Global certificates in multi-fields (ITE 62368-1, Medical 60601-1, Household 60335-1,Industrial 61558-1/-2-16/61010-1/-2-201, Energy converter 62477-1), SEMI F47 at 200Vac
- 200% peak power capability
- High efficiency up to 93%
- Output voltage 0~120% and output current 0~100% programmable
- Current sharing up to 9600W(3+1) for parallel use
- Built in ORing MOS By request, Order NO. : NSP-2400-xxOR/MODOR
- CANBus(Built in) or MODBus protocol (By request)
- -40~85℃ wide range operation temperature(> +60℃ derating)
- Extremely low leakage current<500uA, 2 x MOPP, suitable for BF medical applications
- Built-in constant current limiting circuit
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Built-in remote ON/OFF control/Remote Sense/ DC OK signal
- Auxiliary 5Vdc and 12Vdc
- Over voltage category Ⅲ (OVC Ⅲ)
- Operating altitude up to 5000 meters
- Built-in intelligent fan speed control, low noise <46dB
- Conformal coating
- 5 years warranty
Specifications
OUTPUT
- DC VOLTAGE
- 24V
- CURRENT
- 100A
- CURRENT RANGE
- 0 ~ 100A
- RATED POWER
- 2400W
- PEAK CURRENTNote.2
- 200A
- PEAK POWERNote.2
- 4800W
- RIPPLE & NOISE (max.)Note.3
- 300mVp-p
- VOLTAGE ADJ. RANGE
- 21.6 ~ 28.8V
- VOLTAGE TOLERANCENote.4
- ±1.0%
- LINE REGULATION
- ±0.5%
- LOAD REGULATION
- ±0.5%
- SETUP, RISE TIMENote.5
- 1800ms, 60ms/115Vac; 1800ms, 60ms/230Vac; 1800ms, 60ms/277Vac at full load
- HOLD UP TIME (Typ.)
- 12ms @ 70% load, 8ms @full load
INPUT
- VOLTAGE RANGENote.6
- 85 ~ 305Vac 250 ~ 431Vdc
- FREQUENCY RANGE
- 47 ~ 63Hz
- POWER FACTOR (Typ.)
- 0.98/115Vac 0.95/230Vac 0.93/277Vac at full load
- EFFICIENCY (Typ.)
- 91%
- AC CURRENT (Typ.)
- 17A/115Vac 13A/230Vac 11A/277Vac
- INRUSH CURRENT (Typ.)
- COLD START 30A/115Vac 60A/230Vac 75A/277Vac
- LEAKAGE CURRENT
- Earth leakage current <500μA(rms)@277Vac ; Touch current<100μA(rms) @ 277Vac
PROTECTION
- SHORT CIRCUIT PEAK POWER MODENote.7
- Constant current limiting, unit will shut down after 5 Sec, AC repower on to recover. (2 Sec for 12V/15V models)
- SHORT CIRCUIT CURRENT LIMITING MODENote.7
- Constant current limiting, recovers automatically after abnormal condition is removed
- OVERLOAD PEAK POWER MODENote.8
- From 105% to 200% of rated output power, unit will shut down after 5 seconds of continuous operation. AC repower on to recover. (2 Sec for 12V/15V models)
- OVERLOAD PEAK POWER MODENote.8
- At >200% of rated output power, constant current limiting is activated. Unit will shut down after 5 seconds of continuous operation. AC repower on to recover. (2 Sec for 12V/15V models)
- OVERLOAD CURRENT LIMITING MODENote.8
- Constant current limiting, recovers automatically after abnormal condition is removed
- OVER VOLTAGE
- 29 ~ 37V Protection type : Shut down and latch off output voltage, re-power on to recover
- OVER TEMPERATURE
- Shut down output voltage, recovers automatically after temperature goes down
FUNCTION
- OUTPUT CURRENT PROGRAMMABLE(PC)
- Adjustment of constant current level is allowable between 0 ~ 100% of rated current. Please refer to the User Manual.
- OUTPUT VOLTAGE PROGRAMMABLE(PV)Note.9
- Adjustment of output voltage is allowable to 0 ~ 120% of nominal output voltage. Please refer to the User Manual.
- PARALLEL
- Up to 9600W or (3+1) units. Please refer to the User Manual.
- AUXILIARY POWER
- 5Vaux @ 0.2A Tolerance ±15%, ripple 150mVp-p 12Vaux @ 0.8A Tolerance ±15%, ripple 450mVp-p
- REMOTE CONTROL
- By electrical signal or dry contact Power ON: RC short Power OFF: RC open
- REMOTE SENSE
- Compensate voltage drop on the load wiring up to 0.5Vdc
- DC OK SIGNAL
- Contact rating(max.):5Vdc/10mA resistive load
- CANBus(BUILT-IN) or MODBus(By Request) INTERFACE
- Communication provides functions such as control, setting and monitoring
- FAN NOISE (Typ.)Note.10
- Built-in intelligent fan speed control detect by PSU'S internal temperature
- FAN NOISE (Typ.) 10% load with Ta=25℃
- 38dB
- FAN NOISE (Typ.) 70% load with Ta=25℃
- 44dB
ENVIRONMENT
- WORKING TEMP.
- -40 ~ +85℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 90% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -40 ~ +85℃, 10 ~ 95% RH non-condensing
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 60℃)
- VIBRATION
- 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC(Note 11~13)
- SAFETY STANDARDS
-
Parameter Standard CB IEC62368-1, IEC60335-1, IEC61558-1/-2-16, IEC61010-1/-2-201, IEC60601-1; IEC62477-1 DEKRA BS EN/EN62368-1, BS EN/EN60335-1, BS EN/EN61558-1/-2-16, BS EN/EN61010-1/-2-201, BS EN/EN60601-1(3.2 Version);BS EN/EN62477-1 UL UL62368-1, ANSI/AAMI ES60601-1(3.2 Version),UL61010-1/-2-201 CQC GB4943.1 BSMI CNS15598-1 EAC TP TC 004 SEMI F47 approved KC/BIS KC 62368-1 and BIS IS 13252(Part 1) certified, No stock, contact sales by request - ISOLATION LEVELNote.14
- Primary-Secondary: 2xMOPP, Primary-Earth: 1xMOPP, Secondary-Earth: 1xMOPP
- OVER VOLTAGE CATEGORYNote.15
- IEC/EN 61558-1/-2-16 (OVC Ⅲ , altitude up to 2000M) ; IEC/EN/UL 62368-1 (OVC Ⅱ, altitude up to 5000M) ; IEC/EN 60335-1 (OVC Ⅱ, altitude up to 5000M) ; IEC/EN/ANSI/AAMI ES60601-1 (OVC Ⅱ, altitude up to 4000M) ; IEC/EN/UL 61010-1/-2-201 (OVC Ⅱ , altitude up to 5000M) ; IEC/EN 62477-1 (OVC Ⅱ , altitude up to 5000M)
- SAFETY EXTRA-LOW VOLTAGE(SELV)
- IEC/EN 61558-2-16 (SELV, 12 ~ 60V) ; IEC/EN 60335-1 (SELV, 12 ~ 36V) ; IEC/EN/UL 62368-1 (SELV/ES1, 12 ~ 48V)
- WITHSTAND VOLTAGE
- I/P-O/P:4KVac I/P-FG:2KVac O/P-FG:1.5KVac
- ISOLATION RESISTANCE
- I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSION
-
Parameter Standard Test Level Conducted BS EN/EN55032(CISPR32),CNS 15936,GB/T 9254.1,KS C 9832 Class B Conducted BS EN/EN55014-1(CISPR14-1) Conducted BS EN/EN55011(CISPR11) Class B Radiated BS EN/EN55032(CISPR32),CNS 15936,GB/T 9254.1,KS C 9832 Class B Radiated BS EN/ENEN55014-1(CISPR14-1) Radiated BS EN/EN55011(CISPR11) Class B Harmonic Current BS EN/EN61000-3-2(IEC61000-3-2),GB 17625.1 Class A Voltage Flicker BS EN/ EN61000-3-3(IEC61000-3-3) - EMC IMMUNITY
-
BS EN/EN55035(CISPR35),BS EN/EN61000-6-2(IEC61000-6-2),BS EN/EN60601-1-2(IEC60601-1-2), BS EN/EN55014-2(CISPR14-2),KS C 9835,SEMI F47 tested at 200Vac
Parameter Standard Test Level ESD BS EN/ EN61000-4-2 Level 4, 15KV air; Level 4, 8KV contact Radiated BS EN/ EN61000-4-3 Level 3, 10V/m(80MHz~2.7GHz) Table 9, 9~28V/m(385MHz~5.78GHz) EFT / Burst BS EN/ EN61000-4-4 Level 3, 2KV Surge BS EN/ EN61000-4-5 Level 4, 2KV/Line-Line 4KV/Line-Earth Conducted BS EN/ EN61000-4-6 Level 3, 10V Magnetic Field BS EN/ EN61000-4-8 Level 4, 30A/m Voltage Dips and Interruptions BS EN/ EN61000-4-11 >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods
OTHERS
- MTBF
- 566.1K hrs min. Telcordia SR-332 (Bellcore) ; 47.3K hrs min. MIL-HDBK-217F (25℃)
- DIMENSION (L*W*H)
- 325.8*107*41mm
- PACKING
- 2.32Kg;4pcs/10.3Kg/1.09CUFT
Test conditions and notes15
- 1. All parameters NOT specially mentioned are measured at 230Vac input, rated load and 25℃ of ambient temperature.
- 2. The peak power duration is 2 seconds for 12V/15V models and 5 seconds for all other models.
- 3. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uF & 47uF parallel capacitor.
- 4. Tolerance: includes set up tolerance, line regulation and load regulation.
- 5. Setup time is measured at the first cold start.
- 6. Derating may be required at low input voltages; refer to the "Static Characteristics" section for details.
- 7. Operation under stabilized output voltage may trigger protective shutdown.
- 8. For details on the overload protection mode, refer to the "Overload Protection Mode" section in the User Manual.
- 9. When the output voltage is adjusted via the PV function, the output ripple and noise may exceed the specified limits under certain operating conditions.
- 10. Fan noise measurement is performed in accordance with ISO 7779.
- 11. The Regulatory Compliance Mark (RCM) is applied on a voluntary basis. The equipment meets the relevant IEC or AS/NZS standards, or AS/NZS 3820 where applicable. The use of the RCM mark complies with AS/NZS 4417.1.
- 12. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to "EMI testing of component power supplies." (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf)
- 13. The BIS marking may not be available for certain manufacturing sites or models. Please contact your MEAN WELL sales rep for further information.
- 14. MOPP is suitable for 100-240Vac input only.
- 15. The ambient temperature derating of 3.5℃/1000m with fanless models and 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
Technical drawings
Typical applications
- Industrial automation machinery/ control system
- Security system
- Mechanical and electrical equipment
- Electronic instruments, equipments or apparatus
- Network equipment
- Telecom devices
- Power sourcing equipment of PoE
- Home automation
- Medical devices
- Supercapacitor
Downloads
Datasheet1
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other NSP-2400 Models
6 other models| Model | Power | Voltage | Current | |
|---|---|---|---|---|
| Mean Well NSP-2400-60 2400W 60V Compact Power Supply 40A | 2400W | 60V | 40A | View |
| Mean Well NSP-2400-48 2400W 48V Compact Power Supply 50A | 2400W | 48V | 50A | View |
| Mean Well NSP-2400-36 2397W 36V Compact Power Supply 66.6A | 2397W | 36V | 66.6A | View |
| Mean Well NSP-2400-27 2397W 27V Compact Power Supply 88.8A | 2397W | 27V | 88.8A | View |
| Mean Well NSP-2400-15 2200W 15V Compact Power Supply 146.7A | 2200W | 15V | 146.7A | View |
| Mean Well NSP-2400-12 2200W 12V Compact Power Supply 183.3A | 2200W | 12V | 183.3A | View |
Please log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.