💡 New range: Boke DALI-2 LED drivers | 10–240 W | 5-year warranty Explore the range

Over 15 years experience of providing support of MEAN WELL Power Supplies

Image shown is a representation only. Exact specifications should be obtained from the product datasheet.

Mean Well HRPG-150-12 Power Supply 156W 12V 13A

built-in active PFCPF > 0.95high efficiency up to 90%no load power consumption <0.5W~0.75W1U low profile
SKU HRPG-150-12
Log in to see price Trade pricing & online ordering for account holders
Available to order
|

Overview

HRPG-150-12 is the 12V output model of this series: rated current 13A, rated power 156W, typical efficiency 87%.

Features

  • Universal AC input / Full range
  • Built-in active PFC function, PF>0.95
  • High efficiency up to 88%
  • Withstand 300VAC surge input for 5 seconds
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Built-in constant current limiting circuit
  • 1U low profile 38mm
  • Built-in remote ON-OFF control
  • Stand by 5V@0.3A
  • Built-in remote sense function
  • No load power consumption<0.5W (Note.6)
  • 5 years warranty

Specifications

HRPG-150-12Specifications from the official datasheet (2026-07-13 edition)

OUTPUT

DC VOLTAGE
12V
RATED CURRENT
13A
CURRENT RANGE
0 ~ 13A
RATED POWER
156W
RIPPLE & NOISE (max.)Note.2
120mVp-p
VOLTAGE ADJ. RANGE
10.2 ~ 13.8V
VOLTAGE TOLERANCENote.3
±1.5%
LINE REGULATION
±0.3%
LOAD REGULATION
±0.5%
SETUP, RISE TIME
3000ms, 50ms/230VAC 3000ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)
16ms/230VAC 16ms/115VAC at full load

INPUT

VOLTAGE RANGENote.5
85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
PF>0.95/230VAC PF>0.99/115VAC at full load
EFFICIENCY (Typ.)
87%
AC CURRENT (Typ.)
1.7A/115VAC 0.9A/230VAC
INRUSH CURRENT (Typ.)
35A/115VAC 70A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC

PROTECTION

OVERLOAD
105 ~ 135% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE
14.4 ~ 16.8V Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
Shut down o/p voltage, recovers automatically after temperature goes down

FUNCTION

5V STANDBY
5VSB : 5V@0.3A ; tolerance±5%, ripple : 50mVp-p(max.)
REMOTE CONTROL
RC+ / RC-: 4 ~ 10V or open = power on ; 0 ~ 0.8V or short = power off

ENVIRONMENT

WORKING TEMP.
-40 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY
-40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT
±0.04%/℃ (0 ~ 50℃)
VIBRATION
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes

SAFETY & EMC (Note 4)

SAFETY STANDARDS
UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION
Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY
Compliance to BS EN/ EN61000-4-2,3,4,5,6,8,11, BS EN/ EN55035, BS EN/ EN61000-6-2,heavy industry level,EAC TP TC 020

OTHERS

MTBF
1544.0K hrs min. Telcordia SR-332 (Bellcore) ; 213.4K hrs min. MIL-HDBK-217F (25℃)
DIMENSION
159*97*38mm (L*W*H)
PACKING
0.63Kg; 24pcs/16Kg/0.9CUFT
Test conditions and notes8
  1. 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
  2. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
  3. 3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. 4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
  5. 5. Derating may be needed under low input voltages. Please check the derating curve for more details.
  6. 6. No load power consumption<0.5W when RC- & RC+ (CN100 pin5,6) 0 ~ 0.8V or short.
  7. 7. Strongly recommended that external output capacitance should not exceed 5000uF. (Only for: HRPG-150-3.3/-5/-7.5/-12/-15)
  8. 8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

Technical drawings

HRPG-150-12 Mechanical Specification
Mechanical Specification
HRPG-150-12 Block Diagram
Block Diagram
HRPG-150-12 Derating Curve
Derating Curve
HRPG-150-12 H R P G - 1 5 0 series
H R P G - 1 5 0 series
HRPG-150-12 Function Manual
Function Manual
HRPG-150-12 Function Manual (2)
Function Manual (2)
HRPG-150-12 2.Remote Sense
2.Remote Sense

Downloads

FAQ

Can I use the HRPG-150-12 for a small 12V control panel or industrial electronics assembly?

Yes, this model is a constant-voltage 12V supply rated for 156W and up to 13A. That makes it suitable for smaller 12V industrial control, embedded, or automation loads that stay within that 13A and 156W limit.

Is the HRPG-150-12 a good fit for bench testing or development of 12V embedded hardware?

It can be, because it provides a fixed 12V output with up to 13A available for lab or development setups that stay within 156W. Its 159 x 97 x 38 mm size and 0.63 kg weight also make it easy to place in compact equipment or test fixtures.

Can this power supply run multiple low-to-moderate 12V automation loads from one source?

Yes, as long as the combined 12V demand remains within 13A and 156W. If the total load exceeds either figure, a higher-capacity 12V supply is needed.

Is the HRPG-150-12 suitable for outdoor use or unconditioned spaces?

The specified operating temperature range is -40C to +70C, which supports use across a wide temperature span. No IP rating is provided in the specs, so the product data does not by itself confirm outdoor, wet, or washdown suitability.

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Union Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

{ "id":8343889805611, "variants" :[{ "context":"default", "variant_id": 45321005138219, "sku":"HRPG-150-12", "inventory_qty" : 0, "customer" :false, "custom_html" :"\u003ca class=\"text-current logged-out-price logged-out\" href=\"https:\/\/wellforces.co.nz\/customer_authentication\/redirect?locale=en\u0026region_country=NZ\"\u003e\n \u003cspan \u003ePlease \u003c\/span\u003e \u003cspan class=\"login-text\"\u003eLogin\u003c\/span\u003e \u003cspan\u003e for Pricing\u003c\/span\u003e\n \u003c\/a\u003e", "volume_html" :"\u003cvolume-pricing class=\"parent-display inside_product_form\" id=\"volume-pricing-main\" \u003e\u003c\/volume-pricing\u003e" } ] }
Mean Well HRPG-150-12  Power Supply 156W 12V 13A
Mean Well

Mean Well HRPG-150-12 Power Supply 156W 12V 13A

HRPG-150-12 is the 12V output model of this series: rated current 13A, rated power 156W, typical efficiency 87%.

Features

  • Universal AC input / Full range
  • Built-in active PFC function, PF>0.95
  • High efficiency up to 88%
  • Withstand 300VAC surge input for 5 seconds
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Built-in constant current limiting circuit
  • 1U low profile 38mm
  • Built-in remote ON-OFF control
  • Stand by 5V@0.3A
  • Built-in remote sense function
  • No load power consumption<0.5W (Note.6)
  • 5 years warranty
View product