Over 15 years experience of providing support of MEAN WELL Power Supplies
Overview
LCM-40DA2 is the model of this series: rated power 42W, typical efficiency 91%. Type Blank: standby power consumption <0.5W.
LCM-40DA series is a 40W AC/DC constant current mode output LED driver featuring the multiple levels selectable by dip switch and the DALI interface with the compliance to IEC62386. LCM-40DA operates from 180~295VAC and offers different current levels ranging between 350mA and 1050mA. Thanks to the high efficiency up to 91%, with the fanless design, the entire series is able to operate for -30℃~+90℃ case temperature under free air convection. In addition, LCM-40DA is equipped with push dimming and synchronization functions, so as to provide the optimal design flexibility for LED lighting system.
Features
- Constant current mode output with multiple levels selectable by dip switch
- Emergency lighting application is available according to IEC61347-2-13
- Built-in active PFC function and class II design
- Standby power consumption <0.5W
- Functions: DALI interface(logarithm or linear dimming curve selectable), push dimming synchronization up to 10units
- 3 years warranty
Model encoding
| Type | Function |
|---|---|
| Blank (this model) | standby power consumption <0.5W |
| AUX | standby power consumption <1.2W and Auxiliary DC output(12V/50mA) |
Specifications
OUTPUT
- CURRENT LEVEL
- Current level selectable via DIP switch, please refer to"DIP SWITCH TABLE" section; 350mA / 500mA / 600mA / 700mA(default) / 900mA / 1050mA
- RATED POWER
- 42W
- DC VOLTAGE RANGE
- 2 ~ 100V (350mA) / 2 ~ 80V (500mA) / 2 ~ 67V (600mA) / 2 ~ 57V (700mA) / 2 ~ 45V (900mA) / 2 ~ 40V (1050mA)
- OPEN CIRCUIT VOLTAGE (max.)
- 110V (350mA, 500mA, 600mA) / 65V (700mA, 900mA, 1050mA)
- CURRENT RIPPLENote.5
- 5.0% max. @rated current
- CURRENT TOLERANCE
- ±5%
- SETUP TIMENote.3 Note.9
- 500ms / 230VAC
INPUT
- VOLTAGE RANGENote.2
- 180 ~ 295VAC 254 ~ 392VDC (Please refer to "STATIC CHARACTERISTIC" section)
- FREQUENCY RANGE
- 47 ~ 63Hz
- POWER FACTOR (Typ.)
- PF≧0.975/230VAC, PF≧0.95/277VAC@ full load (Please refer to "POWER FACTOR (PF) CHARACTERISTIC" section)
- TOTAL HARMONIC DISTORTION
- THD< 20%(@load≧75%) (Please refer to “TOTAL HARMONIC DISTORTION(THD)” section)
- EFFICIENCY (Typ.)Note.4
- 91%
- AC CURRENT (Typ.)
- 0.23A/230VAC 0.2A/277VAC
- INRUSH CURRENT (Typ.)
- COLD START 20A(twidth=260μs measured at 50% Ipeak) at 230VAC; Per NEMA 410
- MAX. No. of PSUs on 16A CIRCUIT BREAKER
- 26 units (circuit breaker of type B) / 44 units (circuit breaker of type C) at 230VAC
- LEAKAGE CURRENT
- <0.5mA / 240VAC
- STANDBY POWER CONSUMPTIONNote.6
- <0.5W for Blank-Type
PROTECTION
- SHORT CIRCUIT
- Constant current limiting, recovers automatically after fault condition is removed
- OVER VOLTAGE
- 110 ~ 130V Shutdown o/p voltage, re-power on to recover
- OVER TEMPERATURE
- Shutdown o/p voltage,re-power on to recover
FUNCTION
- DIMMING
- Please refer to "DIMMING OPERATION" section
- SYNCHRONIZATION
- Please refer to "SYNCHRONIZATION OPERATION” section
- TEMP. COMPENSATION
- By external NTC, please refer to “TEMPERATURE COMPENSATION OPERATION”section
ENVIRONMENT
- WORKING TEMP.
- Tcase=-30 ~ +90℃ (Please refer to “ OUTPUT LOAD vs TEMPERATURE” section)
- MAX. CASE TEMP.
- Tcase=+90℃
- WORKING HUMIDITY
- 20 ~ 90% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -40 ~ +80℃, 10 ~ 95% RH
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃)
- VIBRATION
- 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
SAFETY & EMC
- SAFETY STANDARDS
- UL8750(except for DA2-Type), CSA C22.2 No.250.13-12, ENEC BS EN/EN61347-1, BS EN/EN61347-2-13, BS EN/EN62384 independent, GB/T19510.1, GB/T19510.213, BIS IS15885(except for DA2-Type), EAC TP TC 004 approved; According to BS EN/EN61347-2-13 appendix J suitable for emergency installations(EL)(AC Input: 200-240Vac)(for DA2-Type only)
- DALI STANDARDS
- IEC62386-101, 102, 207,251
- WITHSTAND VOLTAGE
- I/P-O/P:3.75KVAC;I/P-DA:1.5KVAC; O/P-DA:1.5KVAC
- ISOLATION RESISTANCE
- I/P-O/P:>100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSIONNote.7
- Compliance to BS EN/EN55015, BS EN/EN61000-3-2 Class C(@load≧40%) ; BS EN/EN61000-3-3; GB/T 17743, GB17625.1, EAC TP TC 020
- EMC IMMUNITY
- Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN61547, light industry level(surge immunity Line-Line 2KV), EAC TP TC 020
OTHERS
- MTBF
- 2271.4K hrs min. Telcordia SR-332 (Bellcore) ; 193.7K hrs min. MIL-HDBK-217F (25℃)
- DIMENSION
- 123.5*81.5*23mm (L*W*H)
- PACKING
- 0.24Kg ; 54pcs/15Kg/1.12CUFT
Test conditions and notes9
- 1. All parameters NOT specially mentioned are measured at 230VAC input, rated current and 25℃ of ambient temperature.
- 2. De-rating may be needed under low input voltages. Please refer to “STATIC CHARACTERISTIC” sections for details.
- 3. Length of set up time is measured at first cold start. Turning ON/OFF the driver may lead to increase of the set up time.
- 4. Efficiency is measured at 500mA/80V output set by DIP switch.
- 5. Current ripple is measured 50%~100% of maximum voltage under rated power delivery.
- 6. Standby power consumption is measured at 180~230VAC.
- 7. The driver is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again. (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf)
- 8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
- 10. To fulfill requirements of the latest ErP regulation for lighting fixtures, this LED power supply can only be used behind a switch without permanently connected to the mains.
Technical drawings
Typical applications
- LED indoor lighting
- LED office lighting
- LED commercial lighting
- LED panel lighting
- Industrial lighting
Downloads
Datasheet1
Certificates4
Test reports1
FAQ
Can I use the LCM-40DA2 for DALI2-controlled LED downlights?
Yes, this model is intended for constant current LED use and includes a DALI interface (IEC62386-101, 102, 207, 251), which makes it relevant for downlight systems that need dimming control. The rated power is 42W, and it should only be matched to constant current LED loads rather than constant voltage products.
Is the LCM-40DA2 a fit for LED signage modules?
It may be a fit only when the signage module is designed for constant current operation and the load matches this driver's listed output characteristics. If the module expects constant voltage power instead, this is the wrong driver type even though it supports selectable current settings by dip switch.
Can this model power a small LED array that needs dimming?
It can work for a small constant current LED array where the load matches the driver's listed output characteristics and the 42W rating. Its DALI interface also makes it relevant where digital dimming is part of the lighting system.
What should I check for LED compatibility with the LCM-40DA2?
Use it only with constant current LEDs and verify that the LED load falls within the DC voltage range for the selected current: 2-100V at 350mA, 2-80V at 500mA, 2-67V at 600mA, 2-57V at 700mA (default), 2-45V at 900mA or 2-40V at 1050mA. The number of LEDs depends on each LED forward voltage, so the correct check is total forward voltage, not a fixed LED quantity.
Is the LCM-40DA2 for indoor or outdoor use?
The spec sheet does not list an IP rating or outdoor suitability, so the protection level has to come from the final fixture or enclosure. Its working temperature is specified as a case temperature (Tcase) of -30°C to +90°C, with 20-90% RH non-condensing humidity.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other LCM Series Models
6 other models| Model | Power | Voltage | Current | IP Rating | |
|---|---|---|---|---|---|
| Mean Well LCM-60 AC-DC Multi-Stage LED driver Constant Current | 60.3W | 102V | 700 Milliampere | IP20 | View |
| Mean Well LCM-40 Power Supply 42W 350mA 500mA 600mA 700mA(default) 900mA 1050mA - Dimmable | 42W | 65V | 700 Milliampere | IP20 | View |
| Mean Well LCM-25 Power Supply 25W 350mA 500mA 600mA 700mA(default) 900mA 1050mA - Dimmable | 18.9W | 41V | 700 Milliampere | IP20 | View |
| Mean Well LCM-25DA2 Power Supply 25W 350mA 500mA 600mA 700mA(default) 900mA 1050mA - DALI2 and Push | 18.9W | 41V | 0.7A | IP20 | View |
| Mean Well LCM-60DA2 Power Supply 60W 500mA 600mA 700mA(default) 900mA 1050mA 1400mA - DALI2 and Push | 60.3W | 95V | 0.9A | IP20 | View |
| Mean Well LCM-40TW Power Supply 42W 350mA 500mA 600mA 700mA(default) 900mA 1050mA - Tunable White | 40W | 53V | 0.7A | IP20 | View |
Please log in to write a review.
Write a review
Reviews are checked before publishing. By submitting you confirm this is your genuine experience with this product.
Submitting your review…
It's published and now helps other buyers.
We're checking it and it'll appear shortly.
Please try again.