💡 New range: Boke DALI-2 LED drivers | 10–240 W | 5-year warranty Explore the range

Over 15 years experience of providing support of MEAN WELL Power Supplies

Image shown is a representation only. Exact specifications should be obtained from the product datasheet.

Mean Well DRC-40A Power Supply 40.02W 13.8V 1.9A

with UPS functionpass LPS
SKU DRC-40A
Log in to see price Trade pricing & online ordering for account holders
Model

Select model — 4 in this family

DRC-40A
Available to order
|

Overview

DRC-40A is the CH1: 13.8V / CH2: 13.8V output model of this series: rated current CH1: 1.9A / CH2: 1A, rated power 40.02W, typical efficiency 86%.

DRC-40 is a 40W AC/DC DIN rail type security power supply series. In addition to the primary output, there is a charger output with a smaller rated current, enabling the backup power supply application the security access systems require. DRC-40 accepts the universal input between 90VAC and 264VAC, and supplies 13.8VDC and 27.6VDC at output, respectively. With the efficiency up to 87%, it can operate with air convection cooling under -30℃ through 70℃. In addition to the key protection features such as overload protection, over voltage protection, battery low cut off, and battery reverse polarity protection (by fuse), the alarm signal for AC OK and battery low signaling is provided, via TTL open collector output for the standard model ( via relay contact output as the optional model), to facilitate the system design.

Features

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage
  • Battery low protection / Battery reverse polarity protection by fuse
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Alarm signal for AC OK and Battery low (via TTL open collector, optional via relay)
  • Cooling by free air convection
  • Pass LPS
  • LED indicator for power on
  • 100% full load burn-in test
  • 3 years warranty

Specifications

DRC-40ASpecifications from the official datasheet (2026-03-31 edition)

OUTPUT

OUTPUT NUMBER
CH1 / CH2
DC VOLTAGE
CH1: 13.8V / CH2: 13.8V
RATED CURRENT
CH1: 1.9A / CH2: 1A
CURRENT RANGE
CH1: 0 ~ 2.9A / CH2: --------
RATED POWER
40.02W
RIPPLE & NOISE (max.)Note.2
CH1: 120mVp-p / CH2: --------
VOLTAGE ADJ. RANGE
CH1:12 ~ 15V
VOLTAGE TOLERANCENote.3
CH1: ±1.0% / CH2: --------
LINE REGULATION
CH1: ±0.5% / CH2: --------
LOAD REGULATION
CH1: ±0.5% / CH2: --------
SETUP, RISE TIMENote.4
400ms, 50ms/230VAC 800ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)
50ms/230VAC 10ms/115VAC at full load

INPUT

VOLTAGE RANGE
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
86%
AC CURRENT (Typ.)
0.8A/115VAC 0.6A/230VAC
INRUSH CURRENT (Typ.)
COLD START 30A/115VAC 60A/230VAC

PROTECTION

OVERLOAD
105 ~ 150% rated output power Protection type : Hiccup mode, recovers automatically after fault condition is removed
OVER VOLTAGE
CH1:14.49 ~ 18.63V Protection type : Shut down o/p voltage, re-power on to recover
BATTERY CUT OFF
10±0.5V

FUNCTION

AC OK
Open collector output, CONTACT : AC OK ; CUT OFF : AC Fail ; max. rating : 50V/30mA
BATTERY LOW
Open collector output, CUT OFF : Battery ; CONTACT : Battery Low ; max. rating : 50V/30mA; Battery low voltage : < 11V

ENVIRONMENT

WORKING TEMP.
-30 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY
-40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT
±0.03%/℃ (0 ~ 55℃) on CH1 output
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes

SAFETY & EMC (Note 5)

SAFETY STANDARDS
UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS 60950.1 approved
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION
Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY
Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61204-3, light industry level, EAC TP TC 020

OTHERS

MTBF
2496.2K hrs min. Telcordia SR-332 (Bellcore) ; 536.6K hrs min. MIL-HDBK-217F (25℃)
DIMENSION
40*90*100mm (W*H*D)
PACKING
0.3Kg; 42pcs/13.6Kg/0.82CUFT
Test conditions and notes8
  1. 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
  2. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
  3. 3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. 4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
  5. 5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
  6. 6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
  7. 7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
  8. 8.The battery voltage is lower than the CUTOFF voltage and cannot perform AC reset charging.

Technical drawings

DRC-40A Block Diagram
Block Diagram
DRC-40A Derating Curve
Derating Curve
DRC-40A D R C - 4 0 series
D R C - 4 0 series
DRC-40A AC OK (Battery low)
AC OK (Battery low)
DRC-40A Mechanical Specification
Mechanical Specification
DRC-40A Installation Instruction
Installation Instruction

Typical applications

  • Security system
  • Emergency lighting system
  • Alarm system
  • DC UPS system
  • Central monitoring system
  • Access systems

Downloads

FAQ

Can I use the DRC-40A for a small 13.8V PLC or relay panel load?

Yes, if the load needs 13.8V constant voltage and stays within 1.9A. The DRC-40A is rated for 40.02W, which makes it suitable for lower-power industrial control and automation loads. It is a DIN rail unit, so it aligns with panel-based applications.

Is the DRC-40A appropriate for compact embedded control systems running on 13.8V DC?

It can be, provided the system requires 13.8V constant voltage and draws no more than 1.9A. The total output rating is 40.02W. That makes it more appropriate for lighter-duty embedded or control electronics than higher-current loads.

Can the DRC-40A be used for low-power security or communications control hardware?

Yes, when the hardware is designed for 13.8V operation and its demand is within 1.9A and 40.02W. The model also includes UPS function, which can matter in backup-oriented control applications. The key requirement is matching the 13.8V constant voltage output.

Is the DRC-40A suitable for indoor panels exposed to low or high temperatures?

Its operating temperature range is -30°C to +70°C, with output derating at higher ambient temperatures per the sheet's derating curve, which supports use across a wide indoor temperature range. No IP rating is listed in the provided specs. That means the product data does not confirm suitability for exposed outdoor or wet environments.

How does the DRC-40A differ from the other DRC series options?

The DRC-40A is the 13.8V, 1.9A, 40.02W version in the DRC-40 series. Its sibling, the DRC-40B, delivers 27.6V at 0.95A with the same 40.02W rating, for 24V battery backup systems instead of 12V ones.

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Union Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

{ "id":8430167687467, "variants" :[{ "context":"default", "variant_id": 45661499785515, "sku":"DRC-40A", "inventory_qty" : 0, "customer" :false, "custom_html" :"\u003ca class=\"text-current logged-out-price logged-out\" href=\"https:\/\/wellforces.co.nz\/customer_authentication\/redirect?locale=en\u0026region_country=NZ\"\u003e\n \u003cspan \u003ePlease \u003c\/span\u003e \u003cspan class=\"login-text\"\u003eLogin\u003c\/span\u003e \u003cspan\u003e for Pricing\u003c\/span\u003e\n \u003c\/a\u003e", "volume_html" :"\u003cvolume-pricing class=\"parent-display inside_product_form\" id=\"volume-pricing-main\" \u003e\u003c\/volume-pricing\u003e" } ] }
Mean Well DRC-40A Power Supply 40.02W 13.8V 1.9A
Mean Well

Mean Well DRC-40A Power Supply 40.02W 13.8V 1.9A

DRC-40A is the CH1: 13.8V / CH2: 13.8V output model of this series: rated current CH1: 1.9A / CH2: 1A, rated power 40.02W, typical efficiency 86%.

DRC-40 is a 40W AC/DC DIN rail type security power supply series. In addition to the primary output, there is a charger output with a smaller rated current, enabling the backup power supply application the security access systems require. DRC-40 accepts the universal input between 90VAC and 264VAC, and supplies 13.8VDC and 27.6VDC at output, respectively. With the efficiency up to 87%, it can operate with air convection cooling under -30℃ through 70℃. In addition to the key protection features such as overload protection, over voltage protection, battery low cut off, and battery reverse polarity protection (by fuse), the alarm signal for AC OK and battery low signaling is provided, via TTL open collector output for the standard model ( via relay contact output as the optional model), to facilitate the system design.

Features

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage
  • Battery low protection / Battery reverse polarity protection by fuse
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Alarm signal for AC OK and Battery low (via TTL open collector, optional via relay)
  • Cooling by free air convection
  • Pass LPS
  • LED indicator for power on
  • 100% full load burn-in test
  • 3 years warranty

Typical applications

  • Security system
  • Emergency lighting system
  • Alarm system
  • DC UPS system
  • Central monitoring system
  • Access systems

Model

  • 40W 13.8V
  • 60W 13.8V
  • 100W 13.8V
  • 180W 13.8
View product