Overview
DRC-60A is the CH1: 13.8V; CH2: 13.8V output model of this series: rated current CH1: 2.8A; CH2: 1.5A, rated power 59.34W, typical efficiency 86%.
DRC-60 is a 60W AC/DC DIN rail type security power supply series. In addition to the primary output, there is a charger output with a smaller rated current, enabling the backup power supply application the security access systems require. DRC-60 accepts the universal input between 90VAC and 264VAC, and supplies 13.8VDC and 27.6VDC at output, respectively. With the efficiency up to 88%, it can operate with air convection cooling under -30℃ through 70℃. In addition to the key protection features such as overload protection, over voltage protection, battery low cut off, and battery reverse polarity protection (by fuse), the alarm signal for AC OK and battery low signalling is provided, via relay contact output, to facilitate the system design.
Features
- Universal AC input / Full range
- Protections: Short circuit / Overload / Over voltage
- Battery low protection / Battery reverse polarity protection by fuse
- Can be installed on DIN rail TS-35/7.5 or 15
- Alarm signal for AC OK and Battery low via relay contact
- Cooling by free air convection
- Pass LPS
- LED indicator for power on
- 100% full load burn-in test
- 3 years warranty
Specifications
OUTPUT
- OUTPUT NUMBER
- CH1, CH2
- DC VOLTAGE
- CH1: 13.8V; CH2: 13.8V
- RATED CURRENT
- CH1: 2.8A; CH2: 1.5A
- CURRENT RANGE
- CH1: 0 ~ 4.3A; CH2: --------
- RATED POWER
- 59.34W
- RIPPLE & NOISE (max.)Note.2
- CH1: 120mVp-p; CH2: --------
- VOLTAGE ADJ. RANGE
- CH1:12 ~ 15V
- VOLTAGE TOLERANCENote.3
- CH1: ±1.0%; CH2: --------
- LINE REGULATION
- CH1: ±0.5%; CH2: --------
- LOAD REGULATION
- CH1: ±0.5%; CH2: --------
- SETUP, RISE TIMENote.4
- 400ms, 50ms/230VAC 800ms, 50ms/115VAC at full load
- HOLD UP TIME (Typ.)
- 50ms/230VAC 10ms/115VAC at full load
INPUT
- VOLTAGE RANGE
- 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
- FREQUENCY RANGE
- 47 ~ 63Hz
- EFFICIENCY (Typ.)
- 86%
- AC CURRENT (Typ.)
- 1.3A/115VAC 0.8A/230VAC
- INRUSH CURRENT (Typ.)
- COLD START 30A/115VAC 60A/230VAC
PROTECTION
- OVERLOAD
- 105 ~ 150% rated output power Protection type : Hiccup mode, recovers automatically after fault condition is removed
- OVER VOLTAGE
- CH1:14.49 ~ 18.63V Protection type : Shut down o/p voltage, re-power on to recover
- BATTERY CUT OFF
- 10±0.5V
FUNCTION
- AC OK
- Relay contact output, ON : AC OK ; OFF : AC Fail ; max. rating : 30V/1A
- BATTERY LOW
- Relay contact output, OFF : Battery OK ; ON : Battery Low ; max. rating : 30V/1A Battery low voltage : < 11V
ENVIRONMENT
- WORKING TEMP.
- -30 ~ +70℃ (Refer to "Derating Curve")
- WORKING HUMIDITY
- 20 ~ 90% RH non-condensing
- STORAGE TEMP., HUMIDITY
- -40 ~ +85℃, 10 ~ 95% RH
- TEMP. COEFFICIENT
- ±0.03%/℃ (0 ~ 50℃) on CH1 output
- VIBRATION
- 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC (Note 5)
- SAFETY STANDARDS
- UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS 60950.1 approved
- WITHSTAND VOLTAGE
- I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
- ISOLATION RESISTANCE
- I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
- EMC EMISSION
- Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
- EMC IMMUNITY
- Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61204-3, light industry level, EAC TP TC 020
OTHERS
- MTBF
- 1854.1K hrs min. Telcordia SR-332 (Bellcore) ; 504.1K hrs min. MIL-HDBK-217F (25℃)
- DIMENSION
- 40*90*100mm (W*H*D)
- PACKING
- 0.3Kg; 42pcs/13.6Kg/0.82CUFT
Test conditions and notes8
- 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μ& 47μF parallel capacitor.
- 3. Tolerance : includes set up tolerance, line regulation and load regulation.
- 4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
- 5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
- 6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
- 7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
- 8.The battery voltage is lower than the CUTOFF voltage and cannot perform AC reset charging.
Technical drawings
Typical applications
- Security system
- Emergency lighting system
- Alarm system
- DC UPS system
- Central monitoring system
- Access systems
Downloads
Certificates6
Test reports1
Catalogues1
FAQ
Can I use the DRC-60A for a 13.8V automation controller or HMI load?
Yes, if the equipment needs 13.8V constant voltage and the load stays within 2.8A. The DRC-60A is rated for 59.34W total, shared between the 2.8A load output and the 1.5A battery charging output. That makes it suitable for mid-range panel power needs.
Is the DRC-60A a good match for 13.8V embedded or industrial electronics in a DIN rail cabinet?
It is a fit when the electronics require 13.8V DC constant voltage and draw no more than 2.8A. The input range is 90-264VAC, and the output capacity is 59.34W. Those ratings suit many enclosed industrial and embedded cabinet applications.
Can the DRC-60A support small battery-backed control systems?
It can be used in systems that need a DIN rail supply with UPS function and a 13.8V output. The available output is 2.8A, with a total power rating of 59.34W. That makes it appropriate for moderate 13.8V control loads rather than high-current equipment.
Will the DRC-60A handle cold or warm indoor operating conditions?
The specified operating temperature is -30°C to +70°C, so it is designed for a broad indoor temperature range. The provided specs do not list an IP rating. Because of that, the data does not confirm use in exposed outdoor or wet locations.
Where does the DRC-60A sit within the DRC family?
The DRC-60 series sheet lists two 59.34W models. The DRC-60A is the 13.8V version (CH1 2.8A, CH2 1.5A, adjustable 12-15V) for 12V batteries, with 86% typical efficiency. The DRC-60B is the 27.6V version (CH1 1.4A, CH2 0.75A, adjustable 24-30V) for 24V batteries, with 88% typical efficiency.
Payment & Security
Payment methods
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.
Other DRC Series Models
7 other models| Model | Power | Voltage | Current | Battery Voltage | |
|---|---|---|---|---|---|
| Mean Well DRC-100A Power Supply 96.6W 13.8V 4.5A | 96.6W | 13.8V | 4.5A | 13.8V | View |
| Mean Well DRC-60B Power Supply 59.34W 27.6V 1.4A | 59.34W | 27.6V | 1.4A | 27.6V | View |
| Mean Well DRC-40A Power Supply 40.02W 13.8V 1.9A | 40.02W | 13.8V | 1.9A | 13.8V | View |
| Mean Well DRC-180B 179.4W 27.6V Power Supply With UPS 4.5A | 179.4W | 27.6V | 4.5A | 27.6V | View |
| Mean Well DRC-100B Power Supply 96.6W 27.6V 2.25A | 96.6W | 27.6V | 2.25A | 27.6V | View |
| Mean Well DRC-180A 179.4W 13.8V Power Supply With UPS 9A | 179.4W | 13.8V | 9A | 13.8V | View |
| Mean Well DRC-40B Power Supply 40.02W 27.6V 950mA | 40.02W | 27.6V | 0.95A | 27.6V | View |